Install an Electric Heat Kit (Strip Heat)
Match the kit kW to the air handler and the electrical service (may need a second circuit), land it per the wiring diagram so sequencers stagger the elements, size the breaker/wire, verify airflow first, then check per-element amp draw and temperature rise.
Approx. 150 min
Before you start
- •Air handler model confirmed as rated to accept the kit kW (the cabinet/coil listing limits max kW); kit voltage (240/208) matches the supply.
- •Electrical service capacity known — a large kit may exceed a single breaker/feeder and require a second circuit (many kits ship with two power blocks/breakers for exactly this).
- •Design heat load and the air handler's rated CFM are known so the temperature rise will land in range.
Tools & materials
Manufacturer wiring diagram for this air handler + kit · Clamp meter (true-RMS) and a voltmeter · Correct breaker(s) and copper conductors sized for the kit MCA · Hand tools, wire connectors, torque screwdriver · Thermometers for supply/return temperature rise