Install a TXV (Thermostatic Expansion Valve)
Mount close to the coil, clamp the sensing bulb on a clean horizontal suction line at 4–5 o'clock and insulate it, tie the external equalizer downstream of the coil, braze with N2 + heat-sink, then set/verify superheat.
Approx. 90 min
Before you start
- •System recovered/isolated so the lines can be opened safely — never braze on a charged system.
- •Correct TXV: matched to refrigerant, capacity/tonnage, and the right bulb charge; internally- vs externally-equalized chosen (most coils with meaningful pressure drop need EXTERNAL equalization).
- •A clean horizontal section of suction line available near the evaporator outlet for the sensing bulb.
Tools & materials
Brazing torch + rod + flux as needed · Tube cutter + deburring tool · Nitrogen + regulator (brazing purge), wet rag/heat-sink compound · Bulb clamp/strap + closed-cell insulation tape · Manifold + pipe-clamp temp probe (for superheat), vacuum pump + micron gauge